Braided Copper Jumpers: Sizing, Terminations and Grounding Requirements

A purchasing drawing specifies a flat copper braid, 25 mm wide and 3 mm thick, with a mounting hole at each end.

One supplier quotes it as a 25 mm² grounding jumper. Another calculates 25 × 3 and offers what it describes as a 75 mm² copper conductor.

Those quotations are not equivalent.

A braided copper jumper is made from interwoven wires, not a solid rectangular bar. Its outside dimensions, actual copper cross-section, terminal construction and installed movement requirements must be specified separately.

For OEM buyers, these distinctions matter when replacing an existing grounding strap or ordering custom braided connections.

Bare flexible copper busbar with copper terminal plates for electrical power connection

Braid Width Is Not Copper Cross-Section

A flat copper braid has spaces between its individual wires. The finished braid also changes shape when compressed, bent or handled.

Therefore, its nominal width and thickness describe its physical envelope, not its solid-metal area.

ABB Furse provides an example in its flexible braid bond catalogue:

ABB product exampleNominal braid envelopeCopper cross-section
FBB-6-200-712 × 1 mm6 mm²
FBB-25-200-1125 × 3 mm25 mm²

Source: ABB Furse — Earth Bonds and Clamps.

These figures describe specific ABB products. They are not standard dimensions that every braid manufacturer must follow.

The second example has a nominal envelope of 75 mm², but only 25 mm² of copper conductor cross-section.

The purchasing consequence: a drawing showing only braid width and thickness does not necessarily establish the conductor size.

When comparing quotations, ask the supplier to identify the specified copper cross-section independently from the braid’s finished outside dimensions.

If a project requires an exact replacement, braid construction and conductor size must not be changed without approval.

The End Connection Is a Separate Design Decision

A copper braid may be correctly specified but still become unsuitable when its terminal construction is changed.

Several manufacturing approaches are used for finished braided jumpers.

ABB Furse supplies flexible copper braid bonds with pressed ferrule terminations.

nVent ERIFLEX also offers braid products with integral, solidified contact palms rather than conventional separately attached terminal lugs.

Other approved constructions may use separately attached copper terminals.

These arrangements should not be treated as identical merely because the exposed braid has the same width.

The termination affects the electrical contact interface, the component’s overall dimensions, its mechanical behavior and the manufacturing inspection required.

For example, replacing a pressed ferrule with an integral palm may change the terminal thickness and the transition between the solid contact area and flexible braid.

That change can affect fastening hardware, clearance and the location where bending occurs.

No single termination method should be declared universally superior without considering the complete application and the manufacturer’s validated construction.

For repeat production, the drawing should identify the approved terminal construction rather than leave this decision to the supplier.

A Flexible Jumper Must Fit Its Installed Route

Braided copper is useful where a rigid conductor would restrict necessary movement or transfer unwanted mechanical loads to a terminal.

However, flexibility alone is not evidence of unlimited fatigue life.

Consider a jumper installed across a movable cabinet connection.

The drawing gives a total length of 200 mm, but it does not show whether that dimension is measured between terminal-hole centers, between terminal ends or across the entire manufactured component.

Two suppliers could interpret that requirement differently and deliver physically different jumpers.

Even if both products fit when the cabinet is closed, one may become excessively tensioned as the door opens.

A proper installation review needs the mounting positions, terminal orientation and the intended path of movement.

Where repeated bending is expected, the braid must be routed so that motion does not concentrate damaging strain at a terminal transition.

The necessary movement range and durability requirements should be established by the equipment designer.

A prototype may need to be evaluated in the actual assembly before repeat production is approved.

The goal is not to make the jumper as long or as flexible as possible. It is to provide an appropriate conductive connection without introducing interference, abrasion or uncontrolled terminal loading.

Grounding Braid or Continuous-Current Connector?

Braided copper is used in both grounding products and power-distribution connectors.

That does not mean the products are automatically interchangeable.

Storm Power Components distinguishes its grounding straps from its flexible power connectors. It expressly states that its particular braided grounding straps are not recommended for continuous-current applications.

This does not establish a universal prohibition on continuous-current braided conductors. Other products are expressly designed and rated for that duty.

Instead, it illustrates why the finished product’s intended electrical function matters.

Intended dutyWhat must be established
Protective bondingCompliance of the complete protective connection with the applicable equipment requirements
Functional or EMC bondingSuitability of the conductor and installation geometry for the required function
Continuous-current connectionCurrent capacity, temperature rise, connection resistance and installed conditions
Movement or vibration accommodationMechanical suitability over the specified movement and service conditions

For machinery, IEC 60204-1:2016+A1:2021 provides an applicable framework for protective bonding within its defined scope.

Other electrical equipment and installations may require different standards.

A manufacturer’s published current value for one braided product must not be interpreted as a universal fault-current rating or as certification of another manufacturer’s jumper.

Similarly, a custom component cannot be claimed to be UL Listed merely because a similar commercial product carries a listing.

The equipment designer must identify the required electrical duty and corresponding acceptance requirements before a manufacturing substitute is approved.

Bare and Tinned Copper: What Actually Changes?

Bare copper and tinned copper braids are both used in electrical connection products.

Tin plating can be selected for surface protection or as part of an approved contact system, depending on the environment and design.

But plating does not replace the need to specify the conductor construction, terminal interfaces or protective electrical performance.

For example, a copper braid exposed to an industrial environment may have acceptable surface protection while its connected terminal still uses an unsuitable contact arrangement.

The mating metals, moisture exposure and approved fastening method must be considered together.

The buyer should distinguish between a braid made from individually tinned copper wires and a finished component with specially treated terminal surfaces.

If surface finish is a controlled requirement, define the applicable areas and process specifications rather than simply writing “tinned copper.”

For protective bonding, the final installation requirements remain separate from the manufacturer’s surface-finish inspection.

Replacement Example: Two 25 mm² Grounding Jumpers

Suppose an equipment manufacturer needs to replace a 25 mm² braided copper grounding jumper with a 200 mm nominal length.

Supplier A offers a flat braid with pressed ferrule ends.

Supplier B offers a braid with integral contact palms.

Both use the same nominal copper section.

Before approving either quotation, the buyer must compare the approved terminal geometry, finished length definition, hole locations and installation routing.

The alternatives may differ in terminal thickness or the location of the rigid-to-flexible transition.

For a stationary connection, those differences may be manageable.

For a frequently moved enclosure part, they may affect the installed bending behavior.

The buyer should also establish whether the component is part of a specified protective bonding system and whether the proposed replacement is permitted.

If the original part belongs to an approved enclosure assembly, the equipment manufacturer’s replacement instructions must be respected.

Matching a braid’s nominal cross-section is therefore necessary where specified, but it is not enough to establish interchangeability.

Inspection Must Cover the Finished Jumper

Inspecting the raw copper braid does not verify the complete jumper.

A production inspection plan may need to address the approved conductor section and construction, finished length, terminal dimensions, hole positions and surface finish.

The ends deserve particular attention because the flexible braid and contact terminals form one manufactured component.

Where the specification requires it, agreed inspections or tests may address terminal attachment integrity or component electrical resistance.

Acceptance limits and methods must be defined for the actual product.

A visually neat braid, a correctly punched hole and an apparently secure terminal are not substitutes for applicable electrical or mechanical performance verification.

For protective bonding installations, the responsible equipment manufacturer or installer must verify the completed protective connection as required by the governing specification.

Carsai’s manufacturing documentation and any additional tests must be confirmed as part of the agreed supply scope.

Specify the Complete Braided Copper Jumper

An effective RFQ describes the assembled part rather than requesting a generic braided copper jumper by length and width.

The drawing should establish the nominal copper conductor section, braid construction, terminal method and finished dimensions.

It should also define the hole pattern, contact surfaces, finish and the intended installation geometry.

For a moving connection, include the mounting arrangement and movement requirements.

State whether the component serves protective bonding, functional bonding or a continuous-current connection, and identify any required approval or verification documentation.

Carsai manufactures custom copper connection components according to customer drawings. Material, termination, finishing and inspection feasibility should be confirmed for each project.

For the broader protective-bonding application, see our Copper Bonding Jumpers for Electrical Grounding Systems guide.

For flexible current-carrying applications, see Braided Copper Flexible Connectors.

Send your braided copper jumper drawing and specifications for a manufacturing quotation.